71
10.2.3 Configure the limit value monitoring for flow for OUT1
►
Select [ou1] and set the switching function: Hno, Hnc, Fno or Fnc
1� When the hysteresis function is selected:
►
Select [SP1] and set the value at which the output is set�
►
Select [rP1] and set the value at which the output is reset�
2� When the window function is selected:
►
Select [FH1] and set the upper limit value of the window�
►
Select [FL1] and set the lower limit value of the window�
Menu CFG:
[ou1]
Main menu:
[SP1]
[rP1]
[FH1]
[FL1]
10.2.4 Configure the limit value monitoring for flow for OUT2
►
Select [SEL2] and set FLOW�
►
Select [ou2] and set the switching function: Hno, Hnc, Fno or Fnc
1� When the hysteresis function is selected:
►
Select [SP2] and set the value at which the output switches�
►
Select [rP2] and set the value at which the output is reset�
2� When the window function is selected:
►
Select [FH2] and set the upper limit value of the window�
►
Select [FL2] and set the lower limit value of the window�
Menu CFG:
[SEL2]
[ou2]
Main menu:
[SP2]
[rP2]
[FH2]
[FL2]
10.2.5 Configure the frequency signal for flow for OUT1
►
Select [ou1] and set FRQ�
►
Select [FEP1] and set the flow value at which the frequency set in FrP1
is provided�
►
Select [FrP1] and set the frequency: 100 Hz���1000 Hz�
[FEP1] is only available if the operating mode GAS or LIQU is
selected�
Menu CFG:
[ou1]
Main menu:
[FEP1]
[FrP1]
10.2.6 Configure the frequency signal for flow for OUT2
►
Select [SEL2] and set FLOW�
►
Select [ou2] and set FRQ�
►
Select [FEP2] and set the upper flow value at which the frequency set in
FrP2 is provided�
►
Select [FrP2] and set the frequency: 100 Hz���1000 Hz�
[FEP2] is only available if the operating mode GAS or LIQU is
selected�
Menu CFG:
[SEL2]
[ou2]
Main menu:
[FEP2]
[FrP2]