77
> The display changes, the indicator LEDs indicate the current display unit�
> After 30 seconds the display changes to the standard display�
11.2 Read the set parameters
►
Briefly press [
●
]
► Press [▼] to select the parameter.
►
Briefly press [
●
]
> The currently set value is displayed for 30 s� Then the unit returns to the pro-
cess value display�
12 Technical data
Technical data and scale drawing at www�autosen�com�
13 Troubleshooting
The unit has many self-diagnostic options� It monitors itself automatically during
operation�
Warnings and error states are displayed, even when the display is switched off�
Error indications are also available via IO-Link�
Display Type
Description
Troubleshooting
Err
Error
• Unit faulty / malfunction�
►
Replace the unit�
No display Error
• Supply voltage too low�
• Setting [diS] = OFF�
►
Check the supply voltage�
► Change the setting [diS] →
10�4�1�
PArA
Error
Parameter setting outside the
valid range�
►
Check parameter setting�
Loc
Warning Setting pushbuttons on the
unit locked, parameter change
rejected�
► Unlock the unit → 10.1.3.
C�Loc
Warning Setting buttons on the unit
temporarily locked, parameter
setting via IO-Link communica-
tion active�
►
Finish parameter setting via
IO-Link communication�
S�Loc
Warning Setting buttons locked via
parameter software, parameter
change rejected�
►
Unlock the unit via IO-Link
interface using the parame-
ter setting software�