DL205 Analog Manual, 7th Edition Rev. D
14-3
Chapter 14: F2-4AD2DA 4-Ch. In / 2-Ch. Out Analog Combination
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
NOTE:
One count in the specifications table is equal to one least significant bit of the analog data value (1 in 4096)
Combination Analog Configuration Requirements
The F2-4AD2DA Analog module requires 16 discrete input and 16 discrete output points.
The module can be installed in any slot of a DL205 system, except when the DL230 CPU
is used. The available power budget may also be a limiting factors. Check the DL205 PLC
User Manual for the particular model of CPU and I/O base being used for more information
regarding power budget and number of local, local expansion or remote I/O points.
Output Specifications
Number of Output Channels
2, single ended (one common)
Range
4–20 mA
Resolution
12 bit (1 in 4096)
Peak Withstanding Voltage
75 VDC, current outputs
External Load Resistance
0
q
minimum, current outputs
Loop Supply Voltage Range
18–30 VDC, current outputs
Maximum Load / Power Supply
910
q
/ 24V, 620
q
/ 18V, 1200
q
/ 30V, current outputs
Linearity Error (best fit)
±1 count (± 0.025% of full scale) maximum
Settling Time
100μs maximum (full scale change)
Maximum Inaccuracy
±0.1% @ 25°C (77°F)
±0.3% 0–60°C (32–140°F)
Full Scale Calibration Error
±5 counts @ 20mA current output
Output Calibration Error
±3 counts @ 4mA current output
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
General Module Specifications
Digital Input and Output Points Required
16 point (X) Inputs
16 point (Y) Outputs
PLC Update Rate
4 input channels/scan max. (D2-240/250-1–1/260 CPU)
2 output channels/scan max. (D2-240/250-1–1/260 CPU)
1 input and 1 output channel/scan max. (D2-230 CPU)
Power Budget Requirement
60mA @ 5VDC (supplied by the base)
External Power Supply Requirement
24VDC, 80mA max. plus 20mA/ loop output
Accuracy vs. Temperature
±45 ppm / °C full scale calibration range
(including maximum offset change).
Operating Temperature
0–60°C (32–140°F)
Storage Temperature
–20–70°C (- 4–158°F)
Relative Humidity
5–95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
MIL STD 810C 514.2
Shock
MIL STD 810C 516.2
Noise Immunity
NEMA ICS3-304