To use the V-memory references required for a DL230 CPU, the first input and output
addresses assigned to the module must be one of the following X and Y locations. The table
also shows the V-memory addresses that correspond to these locations.
Connecting the Field Wiring
Wiring Guidelines
Your company may have guidelines for wiring and cable installation. If so, check the guidelines
before beginning the installation. Here are some general things to consider:
•
Use the shortest wiring route whenever possible.
•
Use shielded wiring and ground the shield at the transmitter source. Do not ground the shield at
both the module and the source.
•
Do not run the signal wiring next to large motors, high current switches, or transformers. This
may cause noise problems.
•
Route the wiring through an approved cable housing to minimize the risk of accidental damage.
Check local and national codes to choose the correct method for your application.
Loop Power Supply Requirements
The F2-4AD2DA requires at least one external power supply for the field devices. The module
requires 24VDC, at 80mA. In addition, each current loop requires 20mA (a total of 120mA
for six current loops). If a separate power supply is used, be sure that it meets these require-
ments.
The DL205 bases have built-in 24VDC power supplies that provide up to 300mA of current.
This may be used instead of a separate supply if only one combination module is used. The
current required is 80mA (module) plus up to 120mA (six current loops) for a total of 200mA.
In some applications, it is desirable to power the loops separately in a location remote from the
PLC. This will work as long as the loop’s power supply meets the voltage and current require-
ments, and its minus (-) side and the module supply’s minus (-) side are connected together.
WARNING: If the internal 24VDC base power is used, be sure to calculate the power budget. Exceeding
the power budget can cause unpredictable system operation that can lead to a risk of personal injury or
equipment damage.
X
X0
X20
X40
X60
X100
X120
X140
X160
V
V40400 V40401 V40402 V40403 V40404 V40405 V40406 V40407
Y
Y0
Y20
Y40
Y60
Y100
Y120
Y140
Y160
V
V40500 V40501 V40502 V40503 V40504 V40505 V40506 V40507
Summary of Contents for DL205
Page 1: ...DL205 Analog I O Manual Manual Number D2 ANLG M ...
Page 2: ...Notes ...
Page 6: ...Notes ...