Analog and Digital Value Conversions
It is sometimes useful to do quick conversions between the signal levels and the digital values.
This can be helpful during startup and/or troubleshooting. The following table shows some
formulas to help with the conversions.
For example, if a 10mA signal level is needed, use
the formula to the right to determine the digital
value “D” to be stored in the V-memory location
which is designated to store the data.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
b
C
D
Range
If the digital value is known
If the analog signal level is known.
4 – 20 mA
A = 16D + 4
65535
D = 65535 (A – 4)
16
D = 65535 (A–4)
16
D = 65535 (10mA–4)
16
D = (4095.94) (6)
D = 24575 (5FFF
h
)