D0–10TD2 DC Output
Outputs per module
10 (sourcing)
Operating voltage range
12–24 VDC
Output voltage range
10.8–26.4 VDC
Peak voltage
50.0 VDC
Maximum output current
0.3 A/point, 1.5 A/common
Minimum output current
0.5 mA
Maximum leakage current
1.5
A @ 30.0 VDC
ON voltage drop
1.0 VDC @ 0.3 A
Maximum inrush current
1 A for 10 ms
OFF to ON response
< 10
s
ON to OFF response
< 60
s
Status indicators
Module activity:
one green LED
Commons per module
2 non–isolated
(5 points/common)
Fuse
N/A
Base power required (5V)
Max. 150 mA (all pts. ON)
Equivalent circuit
Derating Chart
0
10
20
30
40
50 55
Ambient Temperature (
°
C/
°
F)
32
50
68
86
104
122 131
C
°
F
°
Note: The DL05 must have firmware version V4.10 (or later) for this module to function properly.