Installation and
Safety Guidelines
Installing the DeviceNet
Slave Module
2–6
Installing the D0–DEVNETS Slave Module
D0–DEVNETS DeviceNet Slave
Module User Manual, Rev A
Once the D0–DEVNETS is installed in the option slot, set the Node Address. The
Node Address rotary switches are accessed by removing the cover located to the
right of Port1 and Port2 on the DL05.
PORT1 PORT2
RUN
TERM
STOP
Node Address
SW3 X10
SW2 X1
Node Address
Rotary Switches
Remove the cover associated with the option slot where the D0–DEVNETS is
installed in for the DL06 Once the access cover is removed, use a small, flat,
screwdriver to set the Node Address to an
available
address (or MAC ID), from 0 –
63. Note that SW3 sets the tens and SW2 sets the units.
Connect the DeviceNet cable (Belden 3085A, YR–29832 or equivalent) to the
removable connector as shown below. The wire colors are also labeled on the front
of the adapter. Be sure to connect a terminating resistor (121 Ohm 1%, 1/4W). An
external 11–25 VDC power supply is also required.
Connect a terminating
resistor across the CAN
High (white) and CAN
Low (blue) screw
terminals.
The terminating resistor is
121 Ohm 1%, 1/4 Watt. (2
resistors are included with
each D0–DEVNETS).
V– (black)
V+ (red)
CAN* Low (blue)
Shield (bare)
CAN* High (white)
* Controller Area Network (CAN)
Tip:
Be sure that each end of the DeviceNet network ’trunk” has a proper terminating
resistor connected as shown above.
Set the Node
Address
Wiring the Adapter
to a DeviceNet
Network
Summary of Contents for D0-DEVNETS
Page 1: ...D0 DEVNETS DeviceNet Slave Module User Manual Manual Number D0 DEVNETS M...
Page 24: ...1A Specifications In This Appendix Specifications...
Page 27: ...1B Tables In This Appendix DeviceNet Tables...
Page 34: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Page 44: ...1E D0 DEVNETS Think Do Entivity Setup In This Appendix D0 DEVNETS Think Do Entivity Setup...
Page 52: ...1F OIT with D0 DEVNETS In This Appendix OIT with D0 DEVNETS and Think Do Entivity...