Installation and
Safety Guidelines
Installing the DeviceNet
Slave Module
2–12
Installing the D0–DEVNETS Slave Module
D0–DEVNETS DeviceNet Slave
Module User Manual, Rev A
Changing the D0–DEVNETS Setup Parameters
There may be a time when the initial setup parameters will need to be changed. The
following example shows how to edit a DL05/06 PLC program to make the
parameter changes using
Direct
SOFT32 programming software. Once the
following rung is editted, be sure to either power cycle the PLC or put the PLC into
Program mode, then to Run mode. This will insure that the settings will become
effective.
Parameter Example
Function
Register Number
Data Size
Input Point
V40400
2 Bytes
Output Point
V40500
2 Bytes
Input Register
V3000
128 Bytes
Output Register
V3100
128 Bytes
SP0
LDA
LDA
O40500
OUT
V7612
OUT
V7610
LD
K2
OUT
V7615
O40400
LD
K2
OUT
V7611
OUT
V7613
LDA
O3000
OUT
V7614
LD
K128
LDA
O3100
OUT
V7616
LD
K128
OUT
V7617
Load the input starting address and store it
to system memory
Number of input bytes.
Load the output starting address and store it
to system memory.
Number of output bytes.
Load the V–memory location to store the
input data.
Number of input register bytes.
Load the V–memory location to store the
output data.
Number of output register bytes.
Summary of Contents for D0-DEVNETS
Page 1: ...D0 DEVNETS DeviceNet Slave Module User Manual Manual Number D0 DEVNETS M...
Page 24: ...1A Specifications In This Appendix Specifications...
Page 27: ...1B Tables In This Appendix DeviceNet Tables...
Page 34: ...1C Image Table Mapping In This Appendix Image Table Mapping...
Page 44: ...1E D0 DEVNETS Think Do Entivity Setup In This Appendix D0 DEVNETS Think Do Entivity Setup...
Page 52: ...1F OIT with D0 DEVNETS In This Appendix OIT with D0 DEVNETS and Think Do Entivity...