Features and functions of actuator controls
Standard voltages:
1-phase AC current (voltages/frequencies)
230
115
Volt
50/60
50/60
Hz
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
For current consumption, current type, mains voltage and frequency, refer to the name plate
Power supply
24 V DC +20 %/–15 %
Current consumption: With options up to 200 mA
The external power supply must have a reinforced insulation against mains voltage in accord-
ance with IEC 61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance
with IEC 61800-5-1.
External supply of the electron-
ics (option)
Category III according to IEC 60364-4-443
Overvoltage category
Power electronics with integral motor controller
Power electronics
The controls are designed for the rated motor power, refer to name plate
Rated power
●
4 digital inputs (via opto-isolator, with one common)
-
Control voltage 24 V DC, current consumption: approx. 15 mA per input
-
Minimum pulse duration for shortest operation pulse: 100 ms.
-
All digital inputs must be supplied with the same potential.
Assignment for open-close actuators:
-
OPEN, STOP, CLOSE (standard)
-
OPEN, STOP, CLOSE, EMERGENCY (option)
-
OPEN, STOP, CLOSE, MODE in combination with positioner (option)
-
OPEN, EMERGENCY, CLOSE, MODE in combination with positioner (option)
Assignment for modulating actuators:
-
OPEN, STOP, CLOSE, MODE (standard)
-
OPEN, EMERGENCY, CLOSE, MODE
●
Analogue input 0/4 – 20 mA (galvanically isolated)
Used as input signal for position setpoint E1 (in combination with positioner) or as input
signal for motor speed E3.
Control
(input signals)
●
Output contacts:
4 programmable semi-conductor output contacts, per contact max. 24 V DC, 1 A (resistive
load)
-
2 NO contacts with one common
Default configuration: End position OPEN, end position CLOSED
-
1 potential-free NO contact for collective fault signal
Default configuration: Torque fault, motor protection tripped
-
1 potential-free change-over contact
Default configuration: Push button REMOTE
●
Analogue output:
Galvanically isolated position feedback 0/4 – 20 mA (load max. 500
Ω
).
Status signals
(output signals)
Auxiliary voltage 24 V DC, max. 40 mA for supply of control inputs, galvanically isolated from
internal voltage supply
Not available for option "external electronics supply".
Voltage output
●
Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
●
2 multi-colour programmable indication lights:
-
End position CLOSED (yellow), fault/failure (red), end position
OPEN (green), operation mode LOCAL (blue)
Standard:
Local controls
Local controls mounted separately on wall bracket
Option:
45
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Technical data Globe valve actuator