Table 13: Warning signalling via yellow indication light
Signification (default)
Signal
Indication
For reasons of accuracy, we recommend se-
lection of the stroke higher than 60 % of the
maximum turn range.
→
Abort warning: Set again
Low limit Uspan
parameter via AUMA CDT software within the
Position transmitter potentiometer
sub-menu.
→
Remedy warning: Reduce maximum turn
range by replacing the reduction gearing
through the AUMA service.
Warning
Blinking
12.2.
Fuses
12.2.1.
Fuses within the actuator controls
The primary fuse F1 is located on the power board (device protection fuse). It
becomes visible when removing the cover to the controls. The fuse cannot be
replaced. Only by replacing the entire power board can the fuse be exchanged.
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Figure 29: Primary fuse on power board
12.2.2.
Motor protection (thermal monitoring)
In order to protect against overheating and impermissible high surface temperatures
at the actuator, a PTC thermistor is embedded in the motor winding. Motor protection
trips as soon as the max. permissible winding temperature has been reached.
The actuator is stopped and controls signals a fault. The left indication light of the
local controls is blinking in red.
The motor has to cool down before operation can be resumed.
42
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Corrective action