9.5.
Output speed: set
Output speed at output drive is defined by the motor speed.
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode)
Figure 25: Speed switch
[S8]
Output speed
Default value: depending on the order
Setting range: 9 steps (refer to table)
Table 9:
SVC/SVCR 07.5
SVC/SVCR 05.1/07.1
Switch [S8]
Step
Output drive speed [rpm]
0.6
1.6
1
0.8
2.2
2
1.1
3.2
3
1.6
4
4
2.2
5.6
5
3.2
8
6
4
11
7
5.6
16
8
8
22
9
impermissible switch position
0
Setting via software parameters (AUMA CDT)
The motor speed can be modified via the software parameters described hereafter:
Contrary to output speed setting using switch [S8], setting via software parameters
offers the following additional possibilities:
●
different motor speeds for operation modes Local and Remote
●
adjustable motor speed setting
●
motor speed setting (target speed) for operation mode Remote by an external
signal (0/4 – 20 mA) via analogue input AIN 1
Setting parameters
Condition: Switch [S5] is in position ON (software mode).
Device configuration
Motor speed
Speed LOCAL
Speed REMOTE
Speed I/O interface
31
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Commissioning (basic settings of controls)