5.3.
Connection via bayonet connector
Figure 10: Arrangement of connections
[XK1] Power terminals (mains cables)
[XK2] Control contacts
Cross sections:
●
Power terminals: max. 1.5 mm² flexible
●
Control contacts: max. 1.5 mm² flexible
Hazardous voltage at open connector (capacitor discharge)!
Risk of electric shock.
→
After disconnecting the power supply (removing connector for power terminals),
wait at least 5 seconds before touching the pins/sockets.
5.3.1.
Cable connection
Observe prior to connec-
tion
●
Observe permissible cross sections of connectors used.
●
Use suitable crimping tools to connect wires:
-
For screw-type connectors:
e.g. Phoenix 4-arbor crimping pliers
-
For bayonet connectors:
e.g. Cannon four indent crimping tool
●
Observe operation instructions of the connector manufacturer.
●
Upon request, AUMA provide suitable connection sets.
●
For further information refer to separate "Technical data Connector".
●
Use in Ex zone 22 is only possible with straight single connectors and protective
sleeves.
Figure 11: Fitting the protective sleeve (option)
Steps
1.
Connect cables according to order-related wiring diagram.
17
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Electrical connection