9.4.
Torque switching: set
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Once the set tripping torque is reached, the controls automatically switch off the
actuator (overload protection of the valve).
Setting via switches
Condition: Switch [S5] is in position OFF (hardware mode).
Figure 24: Switches for tripping torque
[S6]
Tripping torque in direction OPEN
[S7]
Tripping torque in direction CLOSE
Default value: depending on the order
Setting range: in 8 steps (refer to tables), linear from 40 – 100 % of the maximum
tripping torque.
Table 8:
Tripping torques [Nm]
Switch steps
SVC/SVCR 07.5
SVC/SVCR 07.1
SVC/SVCR 05.1
40
20
10
0 - 1
>
>
>
2 - 3
60
30
15
4
>
>
>
5
80
40
20
6
>
>
>
7
100
50
25
8 - 9
> intermediate value
Setting via software parameters (AUMA CDT)
Condition: Switch [S5] is in position ON (software mode).
Setting parameters
Customer settings
Torque switching
Tripping torque CLOSE (S7)
Tripping torque OPEN (S6)
Default value: depending on the order
Setting ranges: adjustable between 40 – 100 % of the maximum tripping torque
30
SVC 05.1 – SVC 07.5/ SVCR 05.1 – SVCR 07.5
Commissioning (basic settings of controls)