Table 8:
Protection on site
Fuse
2)
3-phase AC motor 380 V – 480 V/50 Hz – 60 Hz
1)
Part-turn actu-
ator
Blow characteristics:
Time-delay (gG)
[A]
Max. current
I
max
[A]
Rated current
I
N
[A]
Consumed rated
power
P
IN
[kW]
Type
6.0
1.3
0.8
0.21
SQVEx 05.2
SQRVEx 05.2
6.0
1.1
0.7
0.17
6.0
1.9
1.3
0.39
SQVEx 07.2
SQRVEx 07.2
6.0
1.0
0.8
0.18
6.0
1.5
1.0
0.21
SQVEx 10.2
SQRVEx 10.2
6.0
1.5
1.0
0.21
SQVEx 12.2
SQRVEx 12.2
6.0
1.5
1.0
0.27
SQVEx 14.2
SQRVEx 14.2
For motor with different current type/mains voltage/mains frequency (refer to motor name plate).
Select fuse referring to the Electrical data sheet.
1)
The actuators are suitable for use in current circuits with a maximum short-circuit 1-phase AC current
value of 5,000 A root-mean-square (R.M.S). The output data of the fuses to be provided on site
2)
must not exceed the following values: 32 A/600 V at a maximum mains short-circuit alternating
current of 5,000 A AC.
Consider the max. current (I
max
) (refer to motor name plate or electrical data sheet)
when selecting the circuit breaker.
We recommend refraining from using residual current devices (RCD). However, if
an RCD is used within the mains, the residual current device must be of type B. DC
current may be present within the PE conductor.
Implementation of overcurrent protection devices is not required. Actuator controls
are equipped with own protection mechanisms, adapted to the actuator system.
Therefore, we recommend refraining from using overcurrent protection devices.
For actuator controls equipped with a heating system and external electronics power
supply, the fuses for the heating system have to be provided by the customer (refer
to wiring diagram F4 ext.)
Table 9:
Fuse for heating system
Designation in wiring diagram = F4 ext.
230 V AC
115 V AC
External power supply
1 A T
2 A T
Fuse
If actuator controls are mounted separately from actuator ( actuator controls on wall
bracket): Consider length and cross section of connecting cable when defining the
protection required.
Potential of customer
connections
Refer to Technical data for options of isolated potentials.
Actuator failure after short-term power supply failure!
If the mains voltage is switched on again too soon after a brief failure, F12 fuse may
blow. F12 fuse is used for protection of the power supply of the switchgear DC link.
The fuse may trip if the DC link is not yet completely de-energised when rebooting
the ACV.
→
Ensure that in the event of a brief mains failure, the mains voltage is only
switched on again after a waiting time of 15 seconds.
22
SQVEx 05.2 – SQVEx 14.2/ SQRVEx 05.2 – SQRVEx 14.2 Control unit: electronic (MWG)
Electrical connection
ACVExC 01.2 Modbus RTU