Depending on the parameter setting (motor protection behaviour), the fault signal is
either automatically reset or the fault signal has to be acknowledged.
The acknowledgement is made:
●
in selector switch position Local control (LOCAL) via push button RESET.
●
In selector switch position Remote control (REMOTE) with Reset command
via fieldbus.
Proof-test motor protection
The functionality of the motor protection must be verified at the latest when performing
the maintenance (refer to chapter <Servicing and maintenance>).
The test is performed by simulating the motor protection signal via actuator controls
local controls:
Required user level:
Specialist (4)
or higher.
Diagnostics M0022
TMS proof test M1950
Test procedure:
1.
Set selector switch to position 0 (OFF).
2.
Return to the main menu and select the simulation value in parameter
TMS
proof test M1950
: Select
Thermal test
.
3.
Activate motor protection simulation: Press
Ok
push button.
The safety function is correct if no fault signal is displayed.
4.
Reset simulation: Press
Ok
push button or exit the simulation menu and reset
the selector switch to its initial position.
82
SQVEx 05.2 – SQVEx 14.2/ SQRVEx 05.2 – SQRVEx 14.2 Control unit: electronic (MWG)
Corrective action
ACVExC 01.2 Modbus RTU