Table 24:
Speed sources
Adjustable internal operating
time
Value
Parameters
Yes
Internal 1
Sp. source LOC OP M1700
Sp. source LOCAL CL M2039
Sp. source REM OP M1701
Sp. source REM CL M2040
Yes
Internal 2
Yes
Internal 3
Yes
2 DigIn: "Internal (1-4)"
Yes
Internal 4
No (external speed source)
Analogue input
No (external speed source)
Fieldbus
For further information on setting the speed sources, refer to Manual (Operation and
Setting):
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter for op-
erating time
3.
Either click via the menu
to the parameter or via direct display
→
Via the menu
:
Customer settings M0041
Speed functions M1699
Operat. time internal1 M1940
Operat. time internal2 M1941
Operat. time internal3 M1942
Operat.time internal4 M1943
Oper. time rem. max. M1946
Oper. time rem. max. M1947
→
Via direct display For this, press and enter ID, e.g.:
M1940
.
➥
Display indicates:
Operat. time internal1
Selection
4.
Select via
Up ▲ Down ▼
:
→
▶ Operat. time internal1 M1940
→
▶ Operat. time internal2 M1941
→
▶ Operat. time internal3 M1942
→
▶ Operat.time internal4 M1943
→
▶ Oper. time rem. max. M1946
→
▶ Oper. time rem. max. M1947
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
6.
Press
Edit
.
➥
Display indicates:
-
Specialist (4) →
continue with step 7
-
in the bottom row
Up ▲ Down ▼ Esc →
continue with step 11
68
SQVEx 05.2 – SQVEx 14.2/ SQRVEx 05.2 – SQRVEx 14.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACVExC 01.2 Modbus RTU