Service conditions
AUMA silver-grey (similar to RAL 7037)
Standard:
Colour
Other colours on request
Option:
AUMA part-turn actuators meet or exceed the lifetime requirements of EN ISO 22153. Detailed inform-
ation can be provided on request.
Lifetime
< 72 dB (A)
Sound pressure level
Other
ATEX Directive 2014/34/EU
Machinery Directive 2006/42/EC
Low Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
RoHS Directive 2011/65/EU
RED Directive 2014/53/EU
EU Directives
Dimensions Part-turn actuators SQVEx 05.2 – SQVEx 14.2/SQRVEx 05.2 – SQRVEx 14.2 with ACVExC
01.2
Electrical data Part-turn actuators SQVEx 05.2 – SQVEx 14.2
Electrical data Part-turn actuators SQRVEx 05.2 – SQRVEx 14.2
Reference documents
14.2.
Technical data Actuator controls
Features and functions
Refer to name plate
Explosion protection
Certificates are attached to the device. All standards applied and their respective issues are indicated
on these certificates.
Certificates and standards
The particular conditions of use are listed on the certificates supplied.
Particular conditions of use
Standard voltages AC:
1-phase AC
Voltages/frequencies
3-phase AC
Voltages/frequencies
220 – 240
110 – 120
Volt
380 – 480
220 – 240
Volt
60
50
60
50
Hz
60
50
60
50
Hz
Permissible variation of mains frequency:
±
5 %
Permissible variation of mains voltage:
±
10 %
–30 % for maximum 10 seconds within a range of 380 V – 480 V with the following restrictions:
●
If required, the motor speed will be reduced down to nominal speed depending on the load of the
actuators used
●
A low mains voltage increases the mains current consumption; a higher mains voltage reduces the
mains current consumption
●
The torque limits of the actuators used might be decreased for a short time, if applicable
Power supply
24 V DC: +20 % / –15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
For external electronics supply, the power supply of integral controls must have an enhanced isolation
against mains voltage in compliance with IEC 61010-1 and the output power be limited to 150 VA.
External supply of the electronics
(option)
The actuator controls are designed for the rated power motor power, refer to motor name plate
Rated power
Via Modbus RTU interface
Control and feedback signals
90
SQVEx 05.2 – SQVEx 14.2/ SQRVEx 05.2 – SQRVEx 14.2 Control unit: electronic (MWG)
Technical data
ACVExC 01.2 Modbus RTU