Connector is suitable for wiring dual pair Profinet cables.
The following tables list the available cable types Profinet types A through C with
regard to the respective application:
Table 8:
Cable types for dual pair Profinet cables
Application type C
Application type B
Application type A
Cable types
Dual pair data cable
Dual pair data cable
Dual pair data cable
Version
special applications (e.g. for contin-
ous movement, vibration or twist-
ing)
flexible installation (e.g. for contin-
ous movement, vibration or twist-
ing after installation)
fixed installation, immobile after
installation
Type of installation
Cable parameter
“Profinet type C”
“Profinet type B”
“Profinet type A”
Designation (minimum)
AWG 22/..
≥
0.318 mm²
AWG 22/7
≥
0.318 mm²
AWG 22/1
≥
0.610 mm²
Cross section
depending on application
5.5 – 8.0 mm
Outer cable diameter
depending on application
1.4
±
0.2 mm
Wire diameter
depending on application
Green RAL6018
Colour of shield
Pair 1: white, blue
Pair 2: yellow, orange
Colour of wire insulation
4
Number of wires
Dual pair or star quad
Cable design
depending on application
Alumium foil + copper braid
Shield
Communication requirements
ISO/IEC 11801 Edition 2.0
IEC 61140-1
IEC 61156-6
(minimum device group 5)
ISO/IEC 11801 Edition 2.0
IEC 61140-1
IEC 61156-5
(minimum device group 5)
Applicable standards
≦
20 ns/100 m
Delay
≥
80 dB at 30 – 100 MHz
“Channel class-D” according to EN 50174-2
Coupling attenuation
Minimum cable spacing
The minimum spacing (according to IEC 61918) required between laying Profinet
cables and other cables must be respected. They are shown in the table below.
Table 9:
Minimum spacing for Profinet cables
Spacing to Profinet cable
Steel cutoff bridge
Aluminium cutoff bridge
Without or with non-metal
cutoff bridge
Signal transmission cables
0 mm
0 mm
0 mm
E.g. other Profinet cables, Profibus cables, data cables
for PCs, programming devices, shielded analogue inputs
Power supply cables
50 mm
100 mm
200 mm
Unshielded power supply cables
0 mm
0 mm
0 mm
Shielded power cables
Further references
Ensure absence of equipotential earth bonding differences between the individual
devices at Profinet (perform an equipotential earth bonding).
Available Profinet recommendations, particularly planning, assembly and
commissioning guidelines of the Profibus User Organisation (PNO)
(www.profibus.com) must be met.
16
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Electrical connection
AC 01.2 Non-Intrusive Profinet