6.
Press
Edit
.
➥
Display indicates:
▶ Specialist (4)
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
The screen indicates the pre-set type of seating (
▶Limit
or
▶Torque
) by means
of a black triangle
▶
.
Change settings
10. Use
Up ▲ Down ▼
to select new setting.
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
11. Confirm selection via
Save
.
➥
The setting for the type of seating is complete.
12. Back to step 4 (CLOSED or OPEN): Press
Esc
.
9.2.
Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0088
.
➥
Display indicates:
Trip torque CLOSE
46
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
Commissioning (basic settings)
AC 01.2 Non-Intrusive Profinet