5.3.1.
Terminal compartment (for mains connection): open
Figure 17: Open mains terminal compartment
[1]
Connection housing
[2]
Screws for frame
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Cable entries for mains connection (power and control contacts)
[7]
Blanking plug
[8]
Cable gland (not included in delivery)
Electric shock due to presence of hazardous voltage!
Failure to observe this warning results in death or serious injury.
→
Disconnect device from the mains before opening.
1.
Loosen screws [2] and remove connection housing [1].
2.
Loosen screws [4] and remove socket carrier [5] from connection housing [1].
3.
Insert cable glands [8] suitable for connecting cables.
➥
The enclosure protection IP… stated on the name plate is only ensured if suit-
able cable glands are used.
Figure 18: Example: Name plate for enclosure protection IP68
4.
Seal unused cable entries [6] with suitable blanking plugs [7].
Information
Fieldbus connection can be accessed separately from the mains connection (refer
to <Fieldbus terminal compartment: open>.
21
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Electrical connection