General data of the Profinet interface
Profinet according to IEC 61158 and IEC 61784
Communication protocol
Star topology, point-to-point wiring
Due to the switch function integrated within the AC 01.2, both line topology and redundant ring topology
(MRP) are available.
Unused network ports can be switched off.
Network topology
Ethernet IEEE 802.3
2-pair cabling in compliance with IEC 61784-5-3 Auto Polarity Exchange, Auto Negotiation and Auto
Crossover are supported.
Connection
2 x Ethernet connection terminals with insulation displacement connection, integral screen with strain
relief, suitable for all Ethernet cable types or 2 x RJ-45
Connection via connector for field assembly, one RJ-45 connector for Cat.5 (K009.706) is included in
the scope of supply of the electrical connection.
Profinet connection
100 Mbits/s (100BASE-TX), full duplex
Transmission rate
Max. 100 m
Cable length
I/O controller (usually the PLC/DCS)
I/O devices (field devices)
I/O supervisor (programming device, PC or HMI for diagnostics/commissioning)
Device classes
Provider - consumer model
Fieldbus access
Version V2.32
Supported Profinet specification
Cyclic Profinet communication (RT)
Acyclic Profinet communication (Read/Write Record)
Supported Profinet functions
Status Alarm
Update Alarm
Port Data Change Notification Alarm
Sync Data Change Notification Alarm
Supported Profinet alarms
ACD (Address Conflict Detection)
ARP (Address Resolution Protocol)
DCP (Discovery and Basic Configuration Protocol)
SNMP (Simple Network Management Protocol)
LLDP (Link Layer Discovery Protocol) in accordance with IEEE 802.1AB
These functions allow assignment of the Profinet device name, a graphic representation of the plant to-
pology, port-granular diagnostics as well as neighbourhood detection as the basis for quick commissioning
and easy device replacement.
Supported network diagnostic and
management protocols
Media Redundancy Protocol in compliance with IEC 62439 (switch function integrated within
AC 01.2)
Standard:
Profinet redundancy
System redundancy S2 Single NAP
Option:
319
Vendor ID
1
Ident Code
AUMA-Actuator-AC01-2
Profinet device type
62976
I&M0 Profile ID:
4
I&M0 Profile Specification Type:
257
I&M0 Version:
30
I&M0 Supported:
Identification & Maintenance proper-
ties
0x013F; 0x0001
Profinet Ident Nr.
0x80010000
DAP (Device Access Point)
CC-B (Conformance Class B) for the Profinet application of the AC actuator controls
CC-C (Conformance Class C) for the integral switch function
Conformance class
III
Netload Class
Via TCP/IP and integral web server possible
Via FDI package & software for diagnostics/commissioning (e. g. Siemens PDM, Emerson AMS)
Device diagnostics via Ethernet
Via GSD (ml) file (available for download at www.auma.com)
Device integration
63
SA 07.2-UW – SA 16.2-UW / SAR 07.2-UW – SAR 16.2-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Profinet
Technical data