6E – Input A Initial Delay
Range:
00:00 - 30:00 (minutes:seconds)
Default:
0 second
Description:
Sets a delay before an input trip can occur, after the soft starter has entered the state selected in 6C.
6F, 6G, 6H, 6I, 6J – Input B Trip
Parameters 6F~6J configure the operation of Input B, in the same way as parameters 6A~6E configure Input A. Refer to Input A for
details.
•
6F
Input B Function
(Default: Input Trip (N/O))
•
6G
Input B Name
(Default: Input Trip)
•
6H
Input B Trip
(
Default: Always Active)
•
6I
Input B Trip Delay
(Default: 0:00)
•
6J
Input B Initial Delay
(Default: 0:00)
6K, 6L – Reserved
These parameters are reserved for future use.
6M – Remote Reset Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the MVE's remote reset input (terminals C41, C42) is normally open or normally closed.
6N, 6O, 6P – Reserved
These parameters are reserved for future use.
6Q – Local/Remote
Options:
LCL/RMT Anytime (default)
LCL/RMT button is always enabled.
LCL/RMT When Off
LCL/RMT button is enabled when the starter is off.
Local Control Only
The LCL/RMT button and remote start/stop inputs are disabled.
Remote Control Only
The START and LCL/RMT) buttons are disabled.
Description:
Selects when the LCL/RMT button can be used to switch between local and remote control, and enables or
disables the local control buttons and remote control inputs.
The STOP button on the controller is always enabled.
The reset input and RESET button on the controller are always enabled.
WARNING
The STOP button on the controller is always enabled. When using two-wire remote control, the soft starter will restart
if the remote start/stop and reset inputs are still active.
6R – Comms in Remote
Options:
Disable Control in RMT
Enable Control in RMT (default)
Description:
Selects whether the starter will accept Start, Stop and Reset commands from the serial communication
network when in Remote mode. The Force Comms Trip and Local/Remote commands are always enabled.