COMMISSIONING
MVE User Manual (710-17074-00G) |
65
4.
Connect the soft starter to the medium voltage supply, and connect the motor to the soft starter. Do not connect motor
to the load (i.e. the motor must be uncoupled from the load).
5.
Use the soft starter to operate the motor and verify that the rotation meets the site requirements with quick start/stop.
6.
Stop the motor.
7.
Connect the MV motor to the load and use the soft starter to operate the motor.
8.
Monitor parameters such as Voltage, Current, and Power. Calibrate the voltage and current readouts as required.
9.
Once calibration is completed, record all parameter settings in
Parameter Defaults
on page 73).
10.
Use the Load/Save Settings menu to save the programmed settings as "User set 1" (see
Load/Save Settings
on page 36).