CONTROLLER
MVE User Manual (710-17074-00G) |
35
Analog I/O State
This screen shows the current status of the Analog I/O.
Analog I/O State
Input: - - - - %
Output A: 04.0mA
NOTE
Input is not supported by this product and this screen will always indicate Input: - - - - %
7.9
Reset Thermal Models
The soft starter's thermal modelling software constantly monitors the motor's performance. This allows the starter to calculate
the motor's temperature and ability to start successfully at any time.
The thermal model for the active motor can be reset if required.
1.
Open the Commissioning Menu.
2.
Scroll to Reset Thermal Models and press .
3.
At the confirmation prompt press STORE to confirm or to cancel the action. You
may have to enter your access code.
Reset Thermal Models
M1 X%
M2 X%
Store to Reset
4.
Select Reset and press .
Selecting Do Not Reset returns to previous screen.
Reset Thermal Models
Do Not Reset
Reset
When the thermal model has been reset, the screen will display a confirmation message
then return to the previous screen.
CAUTION
Resetting the motor thermal model will compromise thermal model protection and may compromise motor life. Only
reset the thermal model in an emergency.
7.10
Programming Menu
The Programming Menu lets you view and change programmable parameters that control how the MVE operates.
You can access the Programming Menu at any time, including while the soft starter is running. Any changes to the start profile
take effect immediately.
To open the Programming Menu, press the MENU button while viewing the monitoring screens.
To navigate through the Programming Menu:
•
to scroll through parameter groups, press the
or
button.
•
to open a submenu, press the button.
•
to view the parameters in a group, press the button.
•
to return to the previous level, press the button.
•
to close the Programming Menu, press repeatedly.
Adjustment Lock
You can lock the Programming Menu to prevent users from altering parameter settings. The adjustment lock can be turned on
and off using parameter 15B.
To lock the programming menu:
1.
Open the Programming Menu.
2.
Open the Extended Menu.
3.
Select 'Advanced'.
4.
Enter the Access Code.
5.
Select parameter 15B
Adjustment Lock
6.
Select and store 'Read Only'.