SPECIFICATIONS
MVE User Manual (710-17074-00G) |
9
Inputs
Inputs on Controller
Start (C23, C24) ................................................................................................................................................. 24 VDC, 8 mA approx
Stop (C31, C32) ................................................................................................................................................. 24 VDC, 8 mA approx
Reset (C41, C42) ............................................................................................................................................... 24 VDC, 8 mA approx
Input A (C53, C54) ............................................................................................................................................. 24 VDC, 8 mA approx
Input B (C63, C64) ............................................................................................................................................. 24 VDC, 8 mA approx
Motor thermistor (B4, B5) .................................................................................................................................... Trip point > 3.6 k
Ω
.......................................................................................................................................................................................................
Reset > 1.6 k
Ω
Inputs on power interface board
Bypass readback input (C73, C74) ................................................................................................................. 24 VDC, 8 mA approx
Fan Fail (C1, C2) ............................................................................................................................................... 24 VDC, 8 mA approx
DOL protection activated (C3, C4) .................................................................................................................. 24 VDC, 8 mA approx
Power supply fail input (C5, C6) ..................................................................................................................... 24 VDC, 8 mA approx
NOTE
All control inputs are potential free. Do not apply external voltage to these inputs.
Outputs
Outputs on Controller
Output Relay A (43, 44) ...................................................................................................................................... Normally Open
Output Relay B (51, 52, 54) ..................................................................................................................................... Changeover
Output Relay C (61, 62, 64) ...................................................................................................................................... Changeover
Analog output (B10, B11) ........................................................................................................................ 0-20 mA or 4-20 mA
Ratings of output relays on Controller
.................................................................................................................................................................. 10 A @ 250 VAC resistive
................................................................................................................................................................... 6 A @ 250 VAC 15 p.f. 0.3
.................................................................................................................................................................... 10 A @ 30 VDC resistive
Outputs on power interface board
Main contactor (13, 14) ..................................................................................................................................... Normally Open
Bypass contactor (23, 24) ................................................................................................................................. Normally Open
Run Output/ PFC (33, 34) .................................................................................................................................. Normally Open
Phase arm power supply control relay output (43, 44) ................................................................................ Normally Open
Environmental
Degree of Protection
Power Assembly .................................................................................................................................................................. IP00
Controller ........................................................................................................................................................... IP54/ NEMA 12
Operating temperature ........................................................................................ - 10 ˚C to + 60 °C, above + 50 °C with derating
Humidity ......................................................................................................................................... 5%~95% Relative Humidity
Storage temperature ............................................................................................................................................ - 25 ˚C to + 70 ˚C
Humidity ......................................................................................................................................... 5%~95% Relative Humidity
Operating Altitude ............................................................................................................. 0~1000 m, above 1000 m with derating
Pollution degree ................................................................................................................................................... Pollution Degree 3
Vibration ............................................................................................................................................ Designed to IEC 60068-2-6-Fc
EMC Emission (Designed to IEC 60947-4-2)
Equipment class (EMC) ........................................................................................................................................................... Class A
Conducted radio frequency emission ................................................................................... 10 kHz to 150 kHz: < 120 - 69 dB µV
..................................................................................................................................................... 0.15 MHz to 0.5 MHz: < 79 dB µV
................................................................................................................................................................. 0.5 to 30 MHz: < 73 dB µV
Radiated radio frequency emission .................................................................................. 0.15 MHz to 30 MHz: < 80-50 dB µV/m
..................................................................................................................................................... 30 to 100 MHz: < 60-54 dB µV/m
............................................................................................................................................. 100 MHz to 2000 MHz: < 54 dB µV/m
This product has been designed as Class A equipment. Use of this product in domestic environments may cause radio
interference, in which case the user may be required to employ additional mitigation methods.