APPENDIX
13.7
UL Compliant Installation
This section details additional requirements and configuration settings for the EMX3 to be UL-compliant. Refer to also
UL Fuse
Selection and Short Circuit Ratings
on page 19.
•
Models EMX3-0023B ~ EMX3-0105B
There is no additional requirement for these models.
•
Models EMX3-0145B ~ EMX3-0425B, EMX3-0255C ~ EMX3-1600C
Use the recommended pressure terminal/connector kit. Refer to
Terminal/Connector Parts
on page 87 for more information.
•
Models EMX3-0500B ~ EMX3-1000B
These models are UL recognised components. Separate cable landing busbars may be required within the electrical cabinet when
terminating cables sized according to the National Wiring Code (NEC) regulations.
•
Terminal/Connector Parts
For models EMX3-0145B~EMX3-0425B and EMX3-0255C~EMX3-1600C to be UL compliant, you must use the recommended
pressure terminal/connector as detailed in the table below.
Models
FLC (A)
No. of wires
Recommended lugs part No.
EMX3-0145B
145
1
OPHD 95-16
EMX3-0170B
170
1
OPHD 120-16
EMX3-0200B
200
1
OPHD 150-16
EMX3-0220B
220
1
OPHD 185-16
EMX3-0255B
255
1
OPHD 240-20
EMX3-0350B
350
1
OPHD 400-16
EMX3-0425B
425
2
OPHD 185-16
EMX3-0255C
255
1
OPHD 240-20
EMX3-0360C
360
2
1 x 600T-2
EMX3-0380C
380
EMX3-0430C
430
EMX3-0620C
620
EMX3-0650C
650
EMX3-0790C
790
4
2 x 600T-2
EMX3-0930C
930
3
2 x 600T-2
EMX3-1200C
1200
4
1 x 750T-4
EMX3-1410C
1410
EMX3-1600C
1600
5
1 x 750T-4
1 x 600T-3
13.8
Disposal Instructions
Equipment containing electrical components may not be disposed of together with domestic waste.
It must be collected separately as electrical and electronic waste according to local and currently
valid legislation.