POWER CIRCUITS
In-line installation, non-bypassed
6/T3
2/T1
5/L3
3/L2
1/L1
13
14
4/T2
E
K1
K1
F1
M
3
K1
Main contactor (optional)
F1
Semiconductor fuses (optional)
13, 14
Relay output A (= Main Contactor,
default)
Inside delta installation, internally bypassed
M
3
6/T3
2/T1
13
14
4/T2
K1
U1(1) U2(4)
V1(2)
V2(5)
W1(3)
W2(6)
5/L3
3/L2
1/L1
E
K1
F1
K1
Main contactor (strongly recommended)
F1
Semiconductor fuses (optional)
13, 14
Relay output A (= Main Contactor,
default)
WARNING
When connecting the EMX3 in inside delta configuration, always install a main contactor or shunt trip circuit breaker.
NOTE
When connecting in inside delta, enter the motor full load current (FLC) for parameter 1A. The EMX3 will automatically
detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.