OPERATION
9.5
Jog Operation
Jog runs the motor at reduced speed, to allow alignment of the load or to assist servicing. The motor can be jogged in either forward
or reverse direction.
CAUTION
Slow speed running is not intended for continuous operation due to reduced motor cooling.
Jog operation causes the motor to heat faster than the rate calculated by the motor thermal model. If you are using
jog, install a motor thermistor or allow sufficient restart delay (parameter 4M).
NOTE
Soft start and soft stop are not available during jog operation.
Jog is only available for the primary motor.
The maximum available torque for jog forward is approximately 50%~75% of motor full load torque (FLT) depending on the
motor. The torque when the motor is jogged in reverse is approximately 25% to 50% of FLT.
Parameter 15E
Jog Torque
controls how much of the maximum available jog torque the soft starter will apply to the motor.
NOTE
Torque settings above 50% may cause increased shaft vibration.
Av
ail
ab
le
to
rq
ue
0%
100%
90%
80%
20%
40%
10%
30%
50%
60%
70%
05723.D
1. Motor FLT
2. Jog forward maximum torque
3. Jog reverse maximum torque
To activate jog operation, use either a programmable input (refer to parameters 6A and 6F, will operate only in Remote Mode) or a
shortcut key (parameters 8B and 8C).
To stop a jog operation, perform one of the following:
•
Remove the jog command.
•
Press the STOP button on the keypad.
Jog will recommence at the end of a restart delay if the jog command is still present. All other commands except the above, will be
ignored during jog operation.
9.6
Inside Delta Operation
Adaptive Control, Jog, Brake and PowerThrough functions are not supported with inside delta (six-wire) operation. If these
functions are programmed when the starter is connected inside delta the behaviour is as given below:
Adaptive Control Start
The starter performs a constant current start.
Adaptive Control Stop
The starter performs a TVR soft stop if parameter 2I
Stop Time
is >0 secs. If parameter 2I is set to
0 secs the starter performs a coast to stop.
Jog
The starter issues a warning with the error message Unsupported Option.
Brake
The starter performs a coast to stop.
PowerThrough
The starter trips with the error message Lx-Tx Shorted.
NOTE
When connected in inside delta, current imbalance is the only phase loss protection that is active during run. Do not
disable current imbalance protection (parameter 4H) during inside delta operation.
NOTE
When connecting in inside delta, enter the motor full load current (FLC) for parameter 1A. The EMX3 will automatically
detect whether the motor is connected in-line or inside delta and will calculate the correct inside delta current level.
User Manual (710-04840-00M) |