PROGRAMMING MENU
7O – Motor Temperature Flag
The EMX3 has a motor temperature flag to give early warning of abnormal operation. The flag can indicate that the motor is
operating above its normal operating temperature but lower than the overload limit. The flag can signal the
situation to external equipment via one of the programmable outputs.
Range:
0% - 160%
Default:
80%
Description:
Sets the level at which the motor temperature flag operates, as a percentage of the motor's thermal capacity.
7P – Analog Output A
Options:
Current (% FLC) (default)
Current as a percentage of motor full load current.
Motor Temp (%)
Motor temperature as a percentage of the motor's thermal capacity.
Motor kW (%)
Measured motor kilowatts, as a percentage of maximum kW.
Motor kVA (%)
Measured motor kilovolt amperes, as a percentage of maximum kVA.
Motor pf
Motor power factor, measured by the soft starter.
Measured motor kW:
√
3 x average current x mains reference voltage x measured power factor
Maximum motor kW:
√
3 x motor FLC x mains reference voltage. Power factor is assumed to be 1
Measured motor kVA:
√
3 x average current x mains reference voltage
Maximum motor kVA:
√
3 x motor FLC x mains reference voltage
Description:
Selects which information will be reported via the analog output.
7Q – Analog A Scale
Range:
0-20 mA
4-20 mA (default)
Description:
Selects the range of the analog output.
7R – Analog A Maximum
Range:
0% - 600%
Default:
100%
Description:
Calibrates the upper limit of the analog output to match the signal measured on an external current measuring
device.
7S – Analog A Minimum
Range:
0% - 600%
Default:
0%
Description:
Calibrates the lower limit of the analog output to match the signal measured on an external current measuring
device.
7T, 7U, 7V, 7W – Analog Output B
Parameters 7T~7W configure the operation of
Analog Output B
, in the same way as parameters 7P~7S configure analog output A.
Refer to
Analog Output A
for details.
Output B is only available if the input/output expansion card has been installed.
8 Display
These parameters allow the keypad to be tailored to individual users' requirements.
8A – Language
Options:
English (default)
Português
Chinese
Français
Español
Italiano
Deutsch
Russian
Description:
Selects which language the keypad will use to display messages and feedback.
8B, 8C – F1 and F2 Button Action
Options:
None
Auto-Start/Stop Menu
Jog Forward
Jog Reverse
Description:
Selects the function of the F1 and F2 buttons on the keypad.
User Manual (710-04840-00M) |