Locate thermostat 48” to 54” above main living area floor on an 
INTERIOR wall when possible.  

 

EXTERIOR wall location must have a 3/4” spacer between 
thermostat and exterior wall. 

 

Follow manufacture’s installation instructions provided with 
thermostat.  

 

OPERATING INSTRUCTIONS 

 

 WARNING 

FIRE OR EXPLOSION 

Do not operate furnace while vehicle is in motion or being towed. 

 

 

During initial firing of this furnace, a burn-off of excess oils 
remaining from manufacturing process may cause smoking or 
fumes for 5-10 minutes.  

 

NOTE: if furnace should lock out, the blower will go off in 3 minutes 
and remain off until unit is reset by reactivating the thermostat. 

 

STOP! Read Users Information Manual supplied with furnace

1. 

Turn the manual valve (if so equipped) or the valve at the outside 
LP tank to the “OFF”” position DO NOT force. NOTE: This furnace 
is equipped with a valve shut-off switch with switch in “OFF” 
position. Gas will not flow to burner nor will the furnace operate. 
Turn switch to “ON” position. 

2. 

Set thermostat above room temperature to begin blower operation. 
A slight delay will occur before the blower comes on. Allow blower 
to run for 1 minute for combustion chamber purge cycle. If blower 
does not come on go to shut down and contact your dealer or a 
local recreational vehicle service agency. 

3. 

After 1 minute, the blower may not be running at this time, move 
thermostat lever below room temperature. Wait approximately 2 
minutes for blower to go off. 

4. 

Open manual shut-off valve (if so equipped) or the valve at the 
outside LP tank. Correct operation characteristics depend on the 
valve being positioned fully open. Never attempt to operate with a 
valve partially closed. Turn shut-off switch to “ON” position. 

5. 

Set thermostat lever to desired setting. If set above room 
temperature, blower will come on. 

6. 

Allow 30 seconds for main burner to light after blower comes on. 
This furnace is equipped with an ignition device which automatically 
lights the burner. DO NOT try to light the burner by hand. 

7. 

If burner does not light, repeat Steps 1 through 5. 

8. 

If after three (3) attempts with no ignition, go to shut down and 
contact your dealer or a local recreational vehicle service agency. 
Do not continue to cycle furnace through thermostat in an attempt to 
get ignition.  

 

TO SHUT DOWN 

 

1. 

Set the thermostat to lowest setting, move lever to “OFF” position. 

2. 

Turn manual shut off valve (if so equipped) to the “OFF” position. 
Do not force. 

 

SYSTEM CHECKS 

 

 WARNING 

FIRE OR EXPLOSION 

Never  check  for  leaks  with  an  open  flame.  Turn  on  the  gas  and  apply 
soapy water to all joints to see if bubbles are formed.

 

 

PROPANE GAS PRESSURE TEST 

 
The furnace and any individual shut-off valve must be disconnected from 
gas supply piping system during any pressure testing of system at test 
pressures of more than 1/2” PSI. 
 
Before furnace is connected, piping systems must be tested to be leak 
free. The test must maintain air pressure of a least 6” of mercury or 3” 
PSI for at least 10 minutes. 
 
The entire piping system must be maintained within a range of 10 to 14” 
WC when all appliances are in operation. Test gas connections for 
leakage with a leak test solution. 

 
 

IGNITION CONTROL DIAGNOSTIC CODES 

The following charts give the diagnostic codes given by the ignition 
control when faults are present. 
 

 

A soft lockout is a condition that is timed and will make additional 
attempts to correct the problem. A hard lookout requires resetting of 
the thermostat or turning the power switch off, then back on. 

 

STANDARD 3 TRIES FOR IGNITION CONTROLS 

 

DIAGNOSTIC CHART 

FAULT 

LED INDICATION 

LOCKOUT 

Internal Circuit Board 
Failure 

Steady On, No Flashing 

Hard 

Limit Switch/Airflow 
Problems 

1-Flash With 3-Second 
Pause 

Soft 

Flame Sense Fault 

2-Flashes With 3-Second 
Pause 

Hard 

Ignition Lockout Fault 

3-Flashes With 3-Second 
Pause 

Soft  

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for AFMD16

Page 1: ... cabinet area as a storage compartment DO NOT vent furnace with venting system serving another appliance DO NOT vent furnace to an outside enclosed porch area DO NOT use for temporary heating of buildings or structures under construction Protect building materials from degrading from flue gas exhaust Protect furnace electrical components from water Compartment must be closed when operating unit Sh...

Page 2: ...1 AFMD20111 AFMD20121 AFMD25111 AFMD25121 AFMD30111 AFMD30121 AFMD35111 AFMD35121 Type of Gas LP Propane LP Propane LP Propane LP Propane LP Propane BTU Input 16 000 20 000 25 000 30 000 34 000 BTU Output 12 160 15 200 19 000 22 800 25 840 Duct Static Pressure 20 WC 10 WC 10 WC 10 WC 10 WC Amperage AMPS 4 2 4 2 7 5 7 5 11 1 Watts 50 50 90 90 132 Power Supply Volt DC 12 12 12 12 12 Return Air 80 in...

Page 3: ...ere wires pipes or other objects will interfere with installation or operation of furnace DO NOT install furnace on material that restricts return air such as directly on carpet or soft material like vinyl If you must install furnace on carpet or soft material install furnace on cleats or on a wood or metal panel extending the full width and depth of furnace plus minimum clearance to combustibles ...

Page 4: ...ezel creating a sealing area 3 Pull furnace forward through cutout about a 1 inch slip bezel around casing and flush inner flange with casing 4 Secure bezel to furnace casing with 6 screws 5 Push furnace and bezel back tight against side wall and secure with 14 screws 6 When installing screws DO NOT deform bezel 7 Connect the gas line to the valve and push the gas line plug into casing opening 8 R...

Page 5: ... needed to maintain installation duct air flow requirements DO NOT install floor registers within 2 feet of return air openings See ducting option from casing top and bottom areas These options can be with flex ducting or by hard ducting installations Hard ducting must be sealed to insure proper operation of the appliance HORIZONTAL OR VERTICAL BOTTOM DISCHARGE Figure 6 Units can be installed as b...

Page 6: ...or servicing Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Disconnect electrical power before servicing CAUTION PROPERTY DAMAGE This connection is for low voltage battery or direct current only Do not connect to 120 or 240 volts AC POWER SUPPLY Atwood Mobile Products highly recommends the use of an electronic solid state converter with clean power...

Page 7: ...come on 6 Allow 30 seconds for main burner to light after blower comes on This furnace is equipped with an ignition device which automatically lights the burner DO NOT try to light the burner by hand 7 If burner does not light repeat Steps 1 through 5 8 If after three 3 attempts with no ignition go to shut down and contact your dealer or a local recreational vehicle service agency Do not continue ...

Page 8: ...8 WIRING AND LADDER DIAGRAM ...

Page 9: ...9 PART DRAWINGS PART LISTS ...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...nt de rangement NE PAS aérer la fournaise avec un système de ventilation pour entretenir un autre appareil NE PAS aérer la fournaise à un endroit extérieur fermé comme une véranda NE PAS utiliser pour le chauffage temporaire de bâtiments ou de structures en construction Protégez les matériaux de construction contre la détérioration par l échappement de gaz à combustion Protégez les composantes éle...

Page 13: ...RTE 15 INSTALLATION DE LA PORTE PLANE 16 OPTIONS DE TUYAUTERIE 16 SYSTÈMES DE TUYAUTERIE FLEXIBLE 16 SYSTÈMES DE CONDUITS SOLIDES POUR LE PLANCHER 16 DÉCHARGE PAR LE BAS HORIZONTALE OU VERTICALE 17 PLAQUE D ADAPTATEUR FLEXIBLE 17 CONNEXION DE GAZ PROPANE 17 CONNEXIONS ÉLECTRIQUES 18 INSTALLATION DU THERMOSTAT 18 INSTRUCTIONS D UTILISATION 18 POUR METTRE HORS TENSION 19 SPÉCIFICATIONS MODÈLES Table...

Page 14: ...roite Toujours installer la fournaise sur un mur avec paroi extérieure NE PAS installer la fournaise près d une chambre à bascule de murs coulissants de portes ou autres projections qui pourraient compromettre l échappement de la fournaise Placez la fournaise vers le milieu du guide pour l installation d une seule fournaise L installation doit être accessible si une réparation est nécessaire pour ...

Page 15: ...sion d air de combustion Fixez au mur avec deux vis non fournies 15 L assemblage du conduit doit maintenir un chevauchement minimum de 1 1 4 po sur le tube d échappement et un minimum de 1 2 po du tube de combustion d air NE PAS excéder l épaisseur du mur 16 Fixez la fournaise au plancher avec deux vis à travers les pieds à l arrière du boitier Pour les appareils à la verticale maintenez la fourna...

Page 16: ...omplètement scellé 11 Fixez le pied de montage au plancher pour une installation horizontale Pour les unités verticales retirez les vis des pieds du boitier et repositionnez le pied pour une surface de montage verticale pour maintenir la fournaise en position 12 Fixez la porte et le conduit avec les 6 vis fournies bonne pression statique OPTIONS DE TUYAUTERIE DÉCHARGE MINIMUM REQUISE Modèles Zone ...

Page 17: ...hez les conduits flexibles de la fournaise à la plaque d adaptateur flexible et fixez le conduit en place sur les deux côtés 8 Des conduits additionnels peuvent être utilisés pour maintenir une bonne pression statique ou telle que désirée VÉRIFICATION DU FLUX D AIR Les appareils sont testés pour une augmentation de la température telle que spécifiée dans le plateau de classement Lorsque l installa...

Page 18: ...de la fournaise 2 Connectez le câble rouge au côté positif du bloc d alimentation 3 Connectez le câble noir à la mise à la terre du bloc d alimentation 4 Connectez le fil bleu marqué positif du thermostat au côté du fil du thermostat en utilisant un fil toronné de 22 18 GA 5 Connectez l autre fil bleu à la tête du thermostat en utilisant un fil toronné d un minimum de 22 18 GA ALIMENTATION ÉLECTRI...

Page 19: ...ve de fermeture automatique individuelle doivent être déconnectées du système de tuyau vers l approvisionnement en gaz durant le test de la pression du système aux tests de pression de plus de 1 2 po PSI Avant de connecter la fournaise le système de tuyaux doit être testé pour les fuites Le test doit maintenir la pression d air à au moins 6 po de mercure ou 3 PSI durant au moins 10 minutes Le syst...

Reviews: