Cooling air flow
(2)
Compressor side
(3)
Outside
4.8
Installation instructions for dryer by-pass
Description
It is not required to connect a bypass, a blind flange is foreseen ex factory. If by-passing of the dryer is required,
connect the compressor to the air net as shown below. The compressed air outlet temperature sensor (G3/8”)
and the pressure transducer (1/4” -18 NPT) must be relocated to the delivery pipe upstream of the shut-off
valve. The new location is indicated by “x”. The temperature sensor and pressure transducer must be positioned
perpendicular to the air flow at all time (as shown).