Atlas Copco strongly recommends that customers do not connect the neutral conductor from the power supply
to the compressor unit. The exposed conductive parts of the installation must be earthed locally. (EN 60204-1
par.: 7.2.3)
Power distribution systems (TN, TT, IT)
According to IEC 60950, there are three main types of power distribution systems: TN, TT and IT. The
electrical installation instructions depend on the type of network of the customer's power supply.
Network type TN (Terra Neutral) :
The TN power distribution system provides a direct earth to the exposed conductive parts of the installation.
The connection is made through the PEN-conductor. Within the TN power distribution system, there are three
sub-types: TN-S, TN-C and TN-C-S, identified according to neutral and protective earth conductors. Nearly
85 % to 90 % of industrial networks are TN type.
Network type TN-S (Terra Neutral-Separate) :
The TN-S power distribution system provides separate neutral and direct earth conductors.
A
Power system earth
B
Exposed conductive parts
Network type TN-C (Terra Neutral-Combined) :
In the TN-C power distribution system, the neutral and the protective earth functions are combined in a single
conductor.
Instruction book
56
APF192090
Summary of Contents for GA 160 VSD
Page 1: ...GA 160 VSD APF192090 Instruction book ...
Page 2: ......
Page 64: ...Instruction book 62 APF192090 ...
Page 66: ...Figure A Instruction book 64 APF192090 ...
Page 67: ...Figure B Instruction book APF192090 65 ...
Page 70: ...Text on figure Instruction book 68 APF192090 ...
Page 77: ...Ref Designation 29 Do not mix oil brands Instruction book APF192090 75 ...
Page 92: ...See Oil specifications Instruction book 90 APF192090 ...
Page 111: ......