www.atestgaz.pl
5.5
Technical specification
Power supply
• Voltage V
cc
• Power
10 – 34 V DC
5 W
Environment
• Ambient temperatures Ta
• Humidity
-10 – +50 °C
10 – 90% long term, without condensation
IP
IP20
Digital input parameters
• R
IN
• Inactive (not negated)
• Active (not negated)
10 kΩ
0 – 1 V
10 – 34 V
Any polarity
Digital output parameters
• Relay
Floating contacts, NO/NC
230 V AC / 3 A
230 V DC / 0.25 A
Not protected against overloading
Digital communication parameters
• Port SBUS
• Electric standard
• Communication protocol
• Port ExBUS
• Electric standard
• Communication protocol
RS - 485
Sigma Bus
RS - 485
Modbus ASCII, 19200 b/s 7E1
optionally:
Modbus RTU, 19200 b/s 8N1
Integrated signalling equipment (optical)
LED controls
Integrated signalling equipment (acoustic)
70dB, 0.1 m distance (only for Sigma MOD LED)
Protection class
III
Dimension
See section 5.6
Acceptable cables
1 – 2 mm
2
Enclosure material
Self-extinguishing PPO
Weight
0.4 kg
Mounting
On DIN-35 / TS35
Table 19: Technical specification
s. 28|31
User Manual: POD-002-ENG R03
Summary of Contents for PW-033-A
Page 40: ...www atestgaz pl Notes...