www.atestgaz.pl
No.
Name
Pin
Description
1
Power Supply
Device supply port. Parameters – see section 5.5
GND
Negative. Both terminals GND are internally connected
+
Positive. Both terminals “+” are internally connected
2
DI
Binary inputs, see section 2.3
1 – 4
External alarm input DI1 – DI4
COM
Common terminal of external alarm
3
Line polarity
Configuration jumpers for the SBUS port. See section 2.6
4
SBUS
System communication port. Used for data exchange between devices in Sigma Gas
system
A
Signal line A
B
Signal line B
GND
Negative supply pole (connected with GND of Power Supply port)
5
ExBUS
Communication port, see section 2.5
A
Signal line A
B
Signal line B
GND
Negative supply pole (connected with GND of Power Supply port)
6
Line polarity
Configuration jumpers for the ExBUS port. See section 2.6
7
R1 – R8
Relay outputs, see section 2.2
COM
Common terminal of relay
NO
Normally open contact of relay
NC
Normally close contact of relay
Table 2: Description of the electric interface
More details about interface connections – see Section 4.
2.2
Relays output R1 – R8
The control unit module has 8 universal relay outputs. These outputs can adopt one of the two statuses:
active or inactive (the active state means that the voltage has been given to the relay coil). Terminals of
relays can switch over to the following positions:
Figure 5: Relays in active and inactive state
Technical specification of outputs – see section 5.5.
s. 10|31
User Manual: POD-002-ENG R03
COM
NC
NO
COM
NC
NO
Active
Inactive