www.atestgaz.pl
The memory map for the GTW functionality
in Control Unit Modules Sigma MOD LCD, Sigma
MOD LED, Sigma MOD DO
1
Memory map
Registers range
Description
40001 – 40064
Status of detectors at channels 1 – 32
40065 – 40066
Status of R1 ÷ R8 outputs and DI1 – DI4 inputs
40067 – 40067
Status of control unit
40068 – 40099
Temperature in measuring head of detectors at channels 1 – 32
43501 – 43503
Interface for execution of operator commands (available only for Sigma MOD LCD)
44001 – 44002
External DI control inputs
1.1
Detectors' statuses (read-only)
Channel No. Register
Name
Description
Type
1
40001
State_A
Detector's status
flags
40002
N
Output signal (concentration)
U16
2
40003
State_A
Detector's status
flags
40004
N
Output signal (concentration)
U16
...
...
...
...
...
32
40063
State_A
Detector's status
flags
40064
N
Output signal (concentration)
U16
State_A – status of a detector at the specific channel. Assignment of the individual bits is listed in the table
below.
Bit
Flag
Description
0
Collective_W1
First warning threshold exceeded
1
Collective_W2
Second warning threshold exceeded
2
Collective_AL
Alarm threshold exceeded
3
Collective_CrFail
Collective information about a critical failure
4
Collective_NonCrFail
Collective information about a non-critical failure
5
-
Unused
6
Gas_HiHi_Range
Gas overload
7
Sensor_Lock
Sensor locked (the last measurement result is stored)
8
Calibration
Calibration mode
1
U16 – unsigned 16-bit number.
Atest-Gaz
A. M. Pachole sp. j.
ul. Spokojna 3, 44-109 Gliwice, Poland
VAT No.: PL 9691433231
tel.: +48 32 238 87 94
fax: +48 32 234 92 71
e-mail: [email protected]
Appendix: PU-Z-006-ENG R03
p. 1|4
Summary of Contents for PW-033-A