Mode 1:
When The value of Axis exceeds the value of set 1 the output is active. If the duration is not entered in, the output
remains active, if the duration is entered, the output is remains active during the entered time and then switches to
passive position.
When the axis value falls below from set value the output is passive without depending on the duration value is
entered.Optionally, histeric and offset values can be entered.
Mode 2:
When the value of Axis exceeds the value of set 1 the output is active. The output remains active unless button
(reset the axis) or reset the signal from the sensor.
If the duration is not entered in, the output remains active, if the duration is entered, the output is remains active
during the entered time and then switches to passive position. The output remains active unless it comes buton (
reset the axis) or reset the signal.Optionally, histeric and offset values can be entered.
Mode 3:
Axis value reaches Set 1 value axis value will be locked and the output is active.The output remains active unless it
comes buton ( reset the axis) or reset the signal andaxis value remains in the locked position.
If the duration is entered, the output is remains active during the entered timeand axis value remains in the locked
position. End of the duration, the output becomes passive and Axis value is reset.Optionally, histeric and offset
values can be entered. Hysteresis lower rate is not used this mode.