Manual mode
The manual mode allows you to test all the units, the alarm contact and the
float switches. The display informs you directly about the current
consumption of the units and as well about the position of the float switches.
The various groups of units are interlocked. Thus, for example, aerators and
clear water pump(s) are not to be taken into operation at the same time.
Press
OK
button to start or stop the respective unit. With float switch ON an
alarm sounds by closed float switch.
If a unit has triggered an error due to overcurrent consumption, it can be
taken into operation only after resetting this error. (see troubleshooting).
The manual mode is independent of the switching status of the
float switches!
Even unused outputs can be connected.
After 10 minutes without pressing any button, an automatic reset from
manual mode into automatic mode takes place.
Following the manual operation, the control continue the program at the
same position where it was before entering into manual mode.
If a unit is manually switched to ON during the settling phase, the remaining
time in settling phase will be set to half settling time.
Info
Shows the actual plant type, the PT number set), the software version
number, the date of commissioning and the serial number (SID).
Date / time
Input / modification of date and time.
Important for correct logbook entries!