Operating instructions AQUAMAX
®
PRO G
ATB WATER GmbH, Südstraße 2, D-32457 Porta Westfalica, www.atbwater.com /
Art.-No.: 9060 0272 / Status: 24 February 2021 / Page 20 from 36
Alarm contact
Activation / deactivation of the potential-free contact for alarm signal.
UV-disinfection
Activation / deactivation of UV disinfection. When enabled, the UV lamp is
controlled in accordance with the specified warm-up time before starting the
clear water pump. UV lamp is switched OFF at the end of the clear water
evacuation.
Sensor: ON/OFF possible activation of the UV sensor.
Imin / Imax UV: If the current consumption of the UV reactor is beyond the
current limits an alarm is generated.
When the UV lamp has reached the end of its service life (default setting
8000 h), a warning appears on the display. Please inform the maintenance
company so that the lamp can be replaced during the next maintenance!
This is confirmed by acknowledging the point "Lamp
change" and the counter is reset to 0.
P-precipitation
Activation / deactivation of phosphate precipitation. If this is activated, a
further phase (time = P - phase) is subsequently added to the final
nitrification before settling phase. Time settings for duration of P-phase,
dosing time, operation time of the aerator/mixer and min/max current limits
are selectable.
Winter operation
In activated winter mode, the aeration times are reduced by 20% in the
months of December, January and February.
Factory settings
All parameters are reset to
standard factory settings (see
appendix).