Installation & Servicing instructions ATAG iC-Range
63
14.3 Weather compensation
To set the boiler to weather compensation, please set parameter 4.2.1 to 3 with an ON/OFF or OpenTherm
controler or to 4 with an ATAG ONE zone or ATAG Cube.
1
Turn the selector wheel to highlight the Parameters Zone you want to set.
In this case
Zone 1 Parameters
.
Press
OK
.
2
Turn the selector wheel to highlight
4.2 Z1 Settings
.
Press
OK
.
3
Turn the selector wheel to highlight
4.2.1 Thermoregulation
.
Press
OK
.
4
Make a choise between
3 Outdoor T Only
or
4 Room + Outdoor T
.