Installation & Servicing instructions ATAG iC-Range
61
14.2 Parameter listing
In the table below you will find a complete overview of all available Parameters
Chapter
Parameter number
Name
Describtion
Unit
Range
Default
2
Boiler Parameters
2.0
General
2.0.0
DHW Set point
Water set point temperature in DHW mode during comfort periods
°C
40‐65 (Combi)
60
40‐65 (combi)
60
2.0.2
Gas Type
0 = Nat Gas
0
1 = LPG
0 ‐ 2
2 = G230
2.0.3
Maximum water temp
maximum absolute water temperature
°C
80‐90
80
2.0.4
Altitude
parameter for altitude compensation
m
0‐7000
0
2.0.5
Fan inc. Percentage
percentage of fan speed increase when reaching ionisation threshold
%
0 ‐ 25
Do Not Change
2.0.6
T‐Gradient
Gradient Function
°C/min
0‐15
5
2.1
Free
2.1.7
pump continious running
0 = Disabled
0‐1
0
1 = Enabled
2.1.8
Pomp mode max DHW
Max pump speed during DHW burning cycle
%
pump mode min ‐ 100%
90
2.2
Settings
2.2.4
Thermoregulation
Thermoregulation function enable 0 = OFF 1 = ON
0 ‐ 1
1
2.2.7
Boiler Hybrid
Used to set the boiler as a part of a hybrid system
0 ‐ 1
0
( Energy manager presence detaction )
2.2.8
Boiler Version
Type of boiler selection
0 ‐ 2
0
0 = Combi
1 = Storage with NTC
2 = Storage with Thermostat
2.3
Central Heating ‐1
2.3.1
Max CH Adjustable
CH power level adjustable by engineer to the level required
%
0 ‐ 100
100
by the building
2.3.7
CH pump overrun
CH post circulation time
Min
0 ‐ 16
1
2.4
Central Heating ‐ 2
2.4.5
Max pump Modulation
Maximum pump speed in CH mode
%
min ‐ 100
95
2.4.6
Min pump Modulation
Minimum pump speed in CH mode
%
25 ‐ Max
50
2.4.9
External Temp correction
Offset of the Outdoor temperature reading
°C
‐3 ‐ +3
0
2.5
Domestic Hot Water
2.5.0
Comfort function
DHW pre‐heating or storage heating operation mode seletion
0 ‐ 2
0
0 = Disabled
1 = Time Based
2 = Always active
2.6
Boiler manual settings
2.6.0
Manual mode activation
to enable or disable manual mode 0 = OFF 1 = ON
0 ‐ 1
0
2.6.1
Pump Control
0 = OFF 1 = ON
0 ‐ 1
0
2.6.2
Fan Control
0 = OFF 1 = ON
0 ‐ 1
0
2.6.3
Diverter valve control
0 = OFF 1 = ON
0 ‐ 1
0
2.6.7
External Pump
0 = OFF 1 = ON
0 ‐ 1
0
2.7
Test & Utilities
2.7.0
Test mode
Chimney sweeper fucntion active 0 = OFF 1 = ON
0 ‐ 1
0
2.7.1
Air purge
Air purge function activation 0 ‐ OFF 1 = ON
0 ‐ 1
0
2.7.3
Force backup
0 = OFF 1 ‐ ON
0 ‐ 1
0
2.7.6
Force restore
1 = OFF 1 ‐ ON
0 ‐ 1
0
2.8
Reset Menu
2.8.0
Reset factory settings
OK = Yes ESC = No
2.9
Others
2.9.0
GPI function
Selected input for GPI function
0 ‐ 2
1
0 = Burner block NO
1 = Burner block NC
2 = DHW Timer
2.9.1
Building Frost protection
0 = OFF 1 = ON
0 ‐ 1
1
Parameters in I‐series boiler