N U M E R I C A L O C / E F P R O T E C T I O N R E L AY AD R 1 4 1 C / 2 4 1 C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page
60/86
9.3
Flow Chart – To Set & To View Relay Settings
Ip> C6 Del = 04.1
Range 0.1 – 99.9s
Ip TMS = x1.00
Range x0.01 – 1.00
Ip> Enable = Yes
01 : YES, 02 : NO
3Io> = 020
Range 10 – 250%
Save Settings ?
Mode for Save
Ip>> = 016
Multiply by 50
Relay Settings
Ip> Enable = NO
Ip>> Enable = NO
3Io> Enable = No
3Io>> Enable = No
Ip Curve = 002
Range C1 – C6
3Io>> Enable = Yes
01 : YES, 02 : NO
Ip>> Delay = 0.01
Range 0 – 2.00s
Ip> 250% t=x1.00
Ip>> 0100%
Ip> = 250
Range 10 – 250%
Password = 0000
Use Inr/Dec
3Io> Enable = Yes
01 : YES, 02 : NO
Ip>> Enable = Yes
01 : YES, 02 : NO
3Io>> = 016
Multiply by 50
3To TMS = x1.00
Range x0.01 – 1.00
3Io>> Delay = 0.01
Range 0 – 2.00s
3Io Curve = 002
Range C1 – C6
3Io> 250% t=x1.00
3Io>> 0100%
Ip>> Delay
= 0.00
3Io>> Delay = 0.00
Ip> Normal Inv. 2
3Io> Normal Inv.1
Ip> C6 Del = 04.6
3Io> C6 Del = 00.7
3Io>C6 Del = 04.1
Range 0.1 – 99.9s
OK