N U M E R I C A L O C / E F P R O T E C T I O N R E L AY AD R 1 4 1 C / 2 4 1 C
ASHIDA Electronics Pvt. Ltd.
Ref: Manual / ADR141C / 241C
Issue: 04D
Date : 10.07.2014
Page
38/86
3Io>> = 001
Multiply by 50
By using the up arrow key (+
/
) or the down arrow key
(
- /
) the desired
3Io>>
can be set. The setting range is
multiply of 50 in steps of 1.
Press the left arrow key (
) the relay will display as follows.
Ip Curve = 006
Range C1
–
C6
By using the up arrow key (+
/
) or the down arrow key
(-
/
) the desired
Ip Curve
can be selected. Six different
types of curves are provided C1 to C6. When the given
value is 0001 curve 1 is selected and when the given value
0002 curve 2 is selected.
In similar manner any desired curve can be selected as
0001 to 0006 correspond respectively with C1 to C6.
Press the left arrow key (
) the relay will display as follows.
Ip>> Delay = 2.00
Range 0 – 2.00s
By using the up arrow key (+
/
) or the down arrow key
(
- /
) the desired
Ip>> Delay
can be selected. The setting
range is from 0 to 2.00s in steps of 0.01s.
Press the left arrow key (
) the relay will display as follows.
3Io>> Delay = 2.00
Range 0 – 2.00s
By using the up arrow key (+
/
) or the down arrow key
(-
/
) the desired
3Io>> Delay
can be selected. The setting
range is from 0 to 2.00s in steps of 0.01s.
Press the left arrow key (
) the relay will display as follows.
Ip> C6 Delay = 99.5
Range 0.1 – 99.9s
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
Ip>C6 Delay
can be selected. Range is
in between 0.1 – 99.9s in steps of 00.1s
Press the left arrow key (
) the relay will display as follows.
3Io Curve = 006
Range C1
–
C6
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
3Io Curve
can be selected. Six different
types of curves are provided C1 to C6. When the given
value is 0001 curve 1 is selected and when the given value
0002 curve 2 is selected.
Press the left arrow key (
) the relay will display as follows