Relay Setting
3Io Curve = 006
Range C1
–
C6
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
3Io Curve
can be selected. Six different
types of curves are provided from C1 to C6. When the
given value is 001, curve 1 is selected and when the given
value 002, curve 2 is selected.
Press the left arrow key (
) the relay will display as follows.
Ip>> Delay = 2.00
Range 0 – 2.00s
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
Ip>> Delay
can be selected. The setting
range is from 0 to 2.00s in steps of 0.01s.
Press the left arrow key (
) the relay will display as follows.
3Io>> Delay = 2.00
Range 0 – 2.00s
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
3Io>> Delay
can be selected. The
setting range is from 0 to 2.00s in steps of 0.01s.
Press the left arrow key (
) the relay will display as follows.
Ip> C6 Delay = 99.5
Range 0.1 – 99.9s
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
Ip>C6 Delay
can be selected. Range is
in between 0.1 – 99.9s in steps of 00.1s
Press the left arrow key (
) the relay will display as follows.
3Io> C6 Delay = 99.5
Range 0.1 – 99.9s
By using the up arrow key (
+ /
) or the down arrow key
(
- /
) the desired
3Io>C6 Delay
can be selected. Range is
in between 0.1 – 99.9s in steps of 00.1s
Press the left arrow key (
) the relay will display as follows.
Save Settings?
Mode for Save
To
Save
any changes,
Press the left arrow key (
) the relay will save the change
and the following message is display.
Note:
If changes made are
not to be saved
press LED
Reset or leave key pad untouched for 100Sec.
OK
This window will flash for moment
The control will return to the main menu