5.2
ELECTRICAL INSTALLATION, cont.
Prepare the power cables by removing approximately 6” of the outer cable insulation (in the case
of SO type portable cables). Strip the insulation back exposing the appropriate amount of the bare
conductor for the chosen 3/8” ring terminals, and for all input, output, and grounding conductors.
Insert the prepared cables and strain relief assemblies into the prepared holes in the cable access
cover. Insert the terminated wire ends into the appropriate input/output terminal block and
tighten. Replace the power cable access cover and front panel using the removed hardware.
FIGURE 4 INPUT AND OUTPUT CONNECTIONS