“AL1d” - ALARM DELAY:
When the alarm condition occurs, delay
counting begins, as programmed on par. “AL1d” (expressed in s)
and the alarm will be activated only after the elapsing of that time.
"AL1i" - ALARM ACTIVATION IN CASE OF MEASUREMENT
ERROR:
This allows one to establish how the alarm have behave in
the event of a measurement error (yES=alarm active; no=alarm
deactivated).
4.10 - PARAMETERS CONFIGURATION BY “A01”
The instrument is equipped with a connector that allows the transfer
from and toward the instrument of the functioning parameters
through the device
ASCON TECNOLOGIC A01
with
5 poles
connector.
This device it’s mainly useable for the serial programming of the
instruments which need to have the same parameters configuration
or to keep a copy of the programming of an instrument and allow its
rapid retransmission.
To use the device A01 it’s necessary that the device or instrument
are being supplied.
Instrument supplied and device not supplied
SUPPLY
Instrument supplied from the device
SUPPLY ADAPTER
AC SUPPLY
12 VDC
To transfer the configuration of an instrument into the device
(UPLOAD)
it is necessary to proceed in the following way:
1) position both dip switch of A01 in the
OFF
mode.
2) connect the device to the instrument TLK plugging the special
connector.
3) verify that the instrument and the device are supplied
4) observe the indication led on the device A 01: if it results green
this means that a configuration is already loaded on the device while
if it results green blinking or red blinking this means that it has not
been loaded any valid configuration on the device .
5) press the button placed on the device.
6) observe the indication led: after having pressed the button, the
led becomes red and therefore, at the end of the data transfer, it
becomes green.
7) now it is possible to disconnect the device.
To transfer the configuration loaded on the device onto an
instrument of the same family
(DOWNLOAD)
, it is necessary to
proceed in the following way:
1) position both dip switch of A01 in the
ON
mode.
2) connect the device to an instrument TLK having the same
features of the one from which has been downloaded the desired
configuration, plugging the special connector.
3) verify that the instrument and the device are supplied
4) observe the indication led on the device A01: it has to result
green, because if the led results green blinking or red blinking, this
means that on the device it has not been downloaded any valid
configuration and therefore it’s useless to continue.
5) if the les results green, press the button placed on the device.
6) observe the indication led: after having pressed the button, the
led becomes red and therefore, at the end of the data transfer, it
becomes green.
7) now it is possible to disconnect the device.
For additional info, please have a look at the A01 instruction
manual.
5 - PROGRAMMABLE PARAMETERS TABLE
Here following are described all the parameters available on the
instrument. Some of them could be not present or because they are
depending on the type of instrument or because they are
automatically disabled as unnecessary.
Group “
]
SP”
(parameters relative to the Set Point)
Par.
Description
Range
Def.
Note
1
SP1
Set Point
SPLL ÷ SPHL
0
2
SPLL
Low Set Point
-1999 ÷ SPHL -1999
3
SPHL
High Set Point
SPLL ÷ 9999
9999
Group“
]
InP”
(parameters relative to the measure input)
Par.
Description
Range
Def.
Note
4
SEnS
Probe type:
J= thermocoupled J
CrAL= termocoupled K
S= thermocoupled S
Ir.J= Infrared Sen. ZIS J
Ir.CA= Infrared Sen.
ZIS K
Pt1= thermoresistance
Pt100
0.50= 0... 50 mV
0.60= 0... 60 mV
12.60= 12... 60 mV
Ptc= thermistor PTC
KTY81-121
ntc= thermistor NTC
103-AT2
0.20= 0... 20 mA
4.20= 4... 20 mA
0.1= 0... 1 V
0.5=0... 5 V
1.5= 1... 5 V
0.10= 0... 10 V
2.10= 2... 10 V
input C:
J / CrAL / S /
Ir.J / Ir.CA /
Pt1 / 0.50 /
0.60 / 12.60
input E :
J / CrAL / S /
Ir.J / Ir.CA /
Ptc / ntc /
0.50 / 0.60 /
12.60
input I :
0.20 / 4.20
input V :
0.1 / 0.5 / 1.5
/ 0.10 / 2.10
J
Ptc
4.20
0.10
5
SSC
Low scale limit in case
of input with V / I
signals
-1999 ÷ FSC
0
6
FSC
High scale limit in case
of input with V / I
signals
SSC ÷ 9999
100
7
dP
Number of decimal
figures
Pt1 / Ptc / ntc:
0 / 1
norm sig.:
0 ÷ 3
0
8
Unit
Temperature unit of
measurement
°C /°F
°C
9
FiL
Input digital filter
0FF÷ 20.0 s
1.0
10
OFSt
Measuring Offset
-1999 ÷ 9999
0
11
rot
Rotation of the
measuring straight line
0.000 ÷ 2.000 1.000
12
OPE
Output power in case of
measuring error
-100 ÷ 100
%
0
Group “
]
Out”
(parameters relative to the outputs)
Par.
Description
Range
Def.
Note
13
O1F
Functioning of output 1:
1.rEG= Control Out 1
2.rEG=Control Out 2
ALno= Alarm Out
normally opened
ALnc= Alarm Out
normally closed
ALni= Alarm Out
normally closed with
reverse led func.
1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
1.rEG
14
O2F
Functioning of output 2:
see “O1F”
1.rEG / 2.rEG
ALno / ALnc
ALni / OFF
ALno
Ascon Tecnologic - TLK 72 B - OPERATING INSTRUCTIONS -