34
7.4 – FUNCTIONAL FEATURES
Control: ON/OFF, single and double action PID
Measurement range: according to the used probe (see range table)
Display resolution: according to the probe used 1/0,1/0,01/0,001
Overall accuracy: +/- 0,15 % fs
Sampling rate: 130 ms.
Serial Interface : RS485 optoisolated
Communication protocol: MODBUS RTU (JBUS)
Baud rate: Programmable from 1200 ... 38400 baud
Compliance: ECC directive EMC 89/336 (EN 61326), ECC directive LV 73/23 and 93/68 (EN 61010-1)
7.5
–
MEASURING RANGE TABLE
INPUT
without D.P.
with D.P.
tc J
“HCFG” = tc
“SEnS” = J
-160 ... 1000 °C
- 256 ... 1832 °F
-160.0 ... 999.9 °C
-199.9 ... 999.9 °F
tc K
“HCFG” = tc
“SEnS” = CrAl
-270 ... 1370 °C
- 454 ... 2498 °F
-199.9 ... 999.9 °C
-199.9 ... 999.9 °F
tc S
“HCFG” = tc
“SEnS” = S
-50 ... 1760 °C
-58 ... 3200 °F
-50.0 ... 1760.0 °C
-58.0 ... 999.9 °F
Pt100 (IEC)
“HCFG” = rtd
“SEnS” = Pt1
-200 ... 850 °C
-328 ... 1562 °F
-99.9 ... 850.0 °C
-99.9 ... 999.9 °F
PTC (KTY81-121)
“HCFG” = rtd
“SEnS” = Ptc
-55 ... 150 °C
-67 ... 302 °F
-55.0 ... 150.0 °C
-67.0 ...302.0 °F
NTC (103-AT2)
“HCFG” = rtd
“SEnS” = ntc
-50 ... 110 °C
-58 ... 230 °F
-50.0 ... 110.0 °C
-58.0 ... 230.0 °F
0 ... 50 mV
“HCFG” = UoLt
“SEnS” = 0.50
-1999 ... 9999
-199.9 ... 999.9
-19.99 ... 99.99
-1.999 ... 9.999
0..20 mA
“HCFG” = I
“SEnS” = 0.20
4..20 mA
“HCFG” = I
“SEnS” = 4.20