Group “rEG”
(parameters relative to the control)
Par.
Description
Range
Def.
Note
58
Cont
Control type
Pid / On.FA On.FS / nr
Pid
59
Func
Functionin mode output 1rEg
HEAt / CooL
HEAt
60
HSEt
ON/OFF control Hysteresis
-1999 ÷ 9999
1
61
Auto
Autotuning Fast enable
OFF / 1 / 2 / 3
1
62
SELF
Selftuning enable
no / yES
no
63
Pb
Proportional band
0 ÷ 9999
50
64
Int
Integral time
OFF ÷ 9999
sec.
200
65
dEr
Derivative time
OFF÷ 9999
sec.
50
66
FuOc
Fuzzy overshoot control
0.00 ÷ 2.00
0,5
67
tcr1
Cycle time of output 1rEg
0.1 ÷ 130.0 sec.
20,0
68
Prat
Power ratio
2rEg / 1rEg
0.0 ÷ 999.9
1.0
69
tcr2
Cycle time of 2rEg
0.1 ÷ 130.0 sec.
10.0
70
rS
Manual reset
-100.0÷100.0 %
0.0
71
SLor
Gradient of rise ramp
0.00 ÷ 99.99
/ InF
unit/min.
InF
72
dur.t
Dwell time
0.00 ÷ 99.59
/ InF
hrs.-min.
InF
73
SLoF
Gradient of fall ramp
0.00 ÷ 99.99
/ InF
unit / min.
InF
74
St.P
Soft-Start power
OFF /
-100 ÷ 100 %
OFF
75
SSt
Soft-Start time
OFF /
0.1÷7.59
/ InF
hrs.-min.
OFF
Group “PAn”
(parameters relative to the user interface)
Par.
Description
Range
Def.
Note
76
USrb
Functioning of key “U”
noF / tunE / OPLO / Aac / ASi / CHSP /
OFF
noF
77
diSP
Variable visualized on the display
dEF / Pou / HbA / HbL / SP.F / SP.o /
AL1 / AL2 / AL3
dEF
78
AdE
Shift value for the shift index functioning
OFF...9999
2
79
Edit
Fast programming of active Set Point and
alarms
SE / AE / SAE / SAnE
SAE
Group “SEr”
(parameters relative to the serial communication)
Par.
Description
Range
Def.
Note
80
Add
Station address in case of serial communication
0 … 255
1
81
baud
Transmission speed (Baud rate)
1200 / 2400 / 9600 / 19.2 / 38.4
9600
82
PACS
Access at the programming through serial port
LoCL / LorE
LorE