![Ascon tecnologic TLK41 Manual Download Page 32](http://html1.mh-extra.com/html/ascon-tecnologic/tlk41/tlk41_manual_2981548032.webp)
32
6 - PROBLEMS, MAINTENANCE AND GUARANTEE
6.1 – ERROR SIGNALLING
:
Error
Reason
Action
- - - -
Probe interrupted
Verify the correct connection between probe and instrument and
then verify the correct functioning of the probe
uuuu
The measured variable is under the
probe’s limits (underrange)
oooo
The measured variable is higher than
the probe’s limits (overrange)
ErAt
Autotuning not possible because the
process value is lower (or higher) than
SP/2 or because it has been activated
the Soft-Start function.
Swap the instrument into OFF control (OFF) and successively into
automatic control (rEG) in order to make disappear the error
message.
Once the error has been found, try to repeat the autotuning.
noAt
Autotuning not finished within 12 hours
Check the functioning of probe and actuator and try to repeat the
autotuning.
LbA
Loop control interrupted
(Loop break alarm)
Check the functioning of probe and actuator and swap the
instrument into (reG) control
ErEP
Possible anomaly of the EEPROM
memory
Push key “P”
In error conditions the instrument provides an output power as programmed on par “OPE” and activates the desired alarms,
if the relative parameters “ALni” have been programmed = yES.
6.2 – CLEANING
We recommend to clean the instrument with a cloth slightly wet of water or not abrasive cleaners or containing solvents
which may damage the instrument.
6.3 – GUARANTEE AND REPAIRS
The instrument is under warranty against construction vices or defected material, noticed within 12 months from delivery
date. The guarantee is limited to the repairs or to the substitution of the instrument. The eventual opening of the housing, the
violation of the instrument or the wrong use and installation of the product means the automatic decay of the guarantee. In
case of defective instrument, noticed within or out of the guarantee period, do contact our sales department to obtain the
shipment authorisation. The defective product must be shipped to GREISINGER with the detailed description of the failures
found and without any fees or charge for GREISINGER, safe different agreements.