"ALnt" – ALARM TYPE :
It's possible to have 6 different behaviours of the alarm output.
LOAb = ABSOLUTE LOW ALARM: The alarm is activated when the process value goes under the alarm set on parameter
"ALn".
HIAb = ABSOLUTE HIGH ALARM: The alarm is activated when the process value goes higher than alarm set on parameter
"ALn".
LHAb = ABSOLUTE BAND ALARM: The alarm is activated when the process value goes under the alarm set on parameter
"ALn" or goes higher than alarm set on parameter "ALnH".
LOdE = DEVIATION LOW ALARM: The alarm is activated when the process value goes under [SP - ALn]
HIdE = DEVIATION HIGH ALARM: The alarm is activated when the process value goes higher than [SP + ALn]
LHdE = DEVIATION BAND ALARM: The alarm is activated when the process value goes under [SP - ALnL] or goes higher
than [SP + ALnH]