5 – PROGRAMMABLE PARAMETERS
Here following are described all the parameters available on the instrument. Some of them could be not present or because
they are depending on the type of instrument or because they are automatically disabled as unnecessary.
5.1 – PARAMETERS TABLE
Group “SP”
(parameters relative to the Set Point)
Par.
Description
Range
Def.
Note
1
nSP
Number of the programmable Set point
1 ÷ 4
1
2
SPAt
Active Set point
1 ÷ nSP
1
3
SP1
Set Point 1
SPLL ÷ SPHL
0
4
SP2
Set Point 2
SPLL ÷ SPHL
0
5
SP3
Set Point 3
SPLL ÷ SPHL
0
6
SP4
Set Point 4
SPLL ÷ SPHL
0
7
SPLL
Low Set Point
-1999 ÷ SPHL
-1999
8
SPHL
High Set Point
SPLL ÷ 9999
9999
Group “InP”
(parameters relative to the inputs)
Par.
Description
Range
Def.
Note
9
HCFG
Input type
tc / rtd / I / UoLt / SEr
tc
10
SEnS
Probe type
tc :
J / CrAL / S / Ir.J / Ir.CA
rtd :
Pt1 / Ptc / ntc
I :
0.20 / 4.20
UoLt :
0.50 / 0.60 /
12.60 / 0.5 / 1.5 / 0.10 / 2.10
J
11
SSC
Low scale limit in case of input with V / I signals
-1999 ÷ FSC
0
12
FSC
High scale limit in case of input with V / I signals
SSC ÷ 9999
0
13
dp
Number of decimal figures
tc/rtd :
0 / 1
UoLt / I / SEr: 0 ÷ 3
0
14
Unit
Temperature unit of measurement
tc/rtd :
°C / °F
°C
15
FiL
Input digital filter
0FF÷ 20.0 sec.
0.1
16
OFSt
Measuring Offset
-1999 ÷ 9999
0
17
rot
Rotation of the measuring straight line
0.000 ÷ 2.000
1.000
18
InE
“OPE” functioning in case of measuring error
Our / Or / Ur
OUr
19
OPE
Output power in case of measuring error
-100 ÷ 100
%
0
Group “Out”
(parameters relative to the outputs)
Par.
Description
Range
Def.
Note
20
O1F
Functioning of output 1
1.rEG / 2.rEG ALno / Alnc
OFF
1.rEG
21
O2F
Functioning of output 2
1.rEG / 2.rEG ALno / Alnc
OFF
ALno
22
O3F
Functioning of output 3
1.rEG / 2.rEG ALno / Alnc
OFF
ALno
23
O4F
Functioning of output 4
1.rEG / 2.rEG ALno / Alnc
OFF
ALno